DALI DT6 and DALI DT8 drivers can be connected to the same Salvador.
Connections C and D are not recommended due to the possibility of erratic behaviour resulting should one or more power supplies fail, or the DALI bus current of 250mA be exceeded. Power supply failures may result in the bus voltage dropping below the level required for reliable DALI communication.
If erratic behaviour of the wired DALI drivers is observed, the first thing to do is check and confirm all DALI wiring is correct and that the bus voltage and current meets the requirements of the DALI drivers connected.