Before troubleshooting specific issues, confirm the DALI system is fundamentally sound, this includes checking the following:
- Power Supply: Only one DALI power supply per line unless using isolated segments.
 - Bus Voltage: 
- Measured bus voltage (use multimeter) at controlled device should be no more than 2 volts less than the nominal specified output voltage of the control device.
 - Ensure, that DALI bus voltage is not too high or too low: 9.5-22.5 Vdc voltage must be present at every driver.
 - Refer bus voltage to the supply voltage of the DALI bus powering device, there should not be more than X V drop in the farthest point of the DALI bus from the powering device.
 - If one or few devices are misbehaving, ensure that those devices receive DALI power.
 
 - Bus Current:
- The DALI bus current is the total current drawn by all devices connected to the DALI line.
 - According to the DALI standard (IEC 62386), the maximum allowed current on a DALI line is 250 mA.
 - If the total current exceeds 250 mA, the system may become unstable or fail to operate correctly.
 - Ensure, that the DALI current available for the bus is not less than required by the connected DALI devices together.
 
 - Wiring: 
- Check for correct polarity (though DALI is polarity-insensitive), no shorts, and proper terminations. DALI wiring maximum length is 300 meters.
 - Important: When using D4i drivers and other polarized devices, ensure that polarity is respected.
 - DALI bus must not be a closed loop
 - Device Count: Ensure no more than 64 devices per DALI line.
 
 
Problem  | Possible cause  | 
Erratic or intermittent communication  | DALI bus voltage too high (9.5-22.5VDC must be present at every driver)  | 
DALI bus voltage too low (9.5-22.5VDC must be present at every driver)  | |
DALI current exceeds 250mA  | |
DALI current too low for the amount of drivers connected  | |
Loose DALI bus connection at one or more drivers  | |
DALI 300m maximum wire length exceeded  | |
DALI bus connected in a closed loop  | |
DALI bus + & - polarity is mixed (if using D4i drivers)  | |
Unapproved power supply used (see DiiA website)  | |
Non certified DALI drivers used (see DiiA website)  | |
Drivers do not respond to Casambi commands  | See all options from the "Erratic or intermittent communication" section  | 
Driver faulty  | |
DALI bus is not connected to the driver  | |
Cannot address all drivers  | Driver not powered  | 
Driver not connected to the DALI bus  | |
Number of drivers exceeds the Salvador specification  | |
DALI bus connected in a closed loop  | 
DALI Certification
- Devices used should be DALI-2 certified (or DALI-1 if legacy)
 - Certification ensures that the device complies with IEC 62386 standard and has passed interoperability testing.
 - Certified devices are listed on the DALI Alliance Product Database.