Hardware Setup
- Connect the Gateway: Plug the gateway into your network using the RJ-45 port. Power is supplied via PoE (Power over Ethernet).
- Check the 4 status LEDs:
- Operating LED: Flashes green (1 sec interval) when running.
- Network Status: Yellow when network is connected.
- UDP LED: Red (no UDP connection), Green (UDP established).
- TCP/IP LED: Red (no TCP/IP), Green (TCP/IP established). Note: The gateway acts as a TCP client, not a TCP server.
- Mounting: Ensure the device is securely mounted and accessible for network cabling.
Initial Network Configuration
- Default IP: Out-of-the-box, the gateway is set to DHCP. If no DHCP server is present, it defaults to 192.168.1.90.
- Access Web Interface: Use a browser to access the gateway’s IP address.
- Set Login Credentials: On first access, set a username and password for the web interface.
Firmware & Profile
- Check Firmware: Ensure the gateway firmware matches your Casambi network version:
- Firmware 4.XX is for Casambi Evolution ≥ 39.50.
- Profile Selection: In the Casambi app, select the correct profile for your hardware revision (e.g., Ethernet_Gateway_REV2.5).
Casambi App Integration
- Add Device: Pair the gateway to your Casambi network via the app. In the Casambi app, add the gateway as a Bluetooth device. It will appear as a lamp, sensor, and switch.
- Profile Options: Choose the appropriate profile:
- _EVO = 32 groups/scenes, 8 keys.
- _EVO_Groups = 64 groups, 8 keys.
- _EVO_Scenes = 64 scenes, 8 keys.
- Configure as Needed: Set up as lamp, button, PIR sensor, or lux sensor as required.
Basic Settings
- Network: Set static IP, subnet, gateway, and DNS if needed.
- NTP Client: Configure time synchronization if required.
- System: Use the wizard for control system setup (Netcomposer, ArtNet, UDP/TCP, etc.).
- Casambi Settings: Confirm network connection and polling method (active, passive, etc.).
Testing & Identification
- Identify Device: Use the app or web interface to activate identify mode (LEDs will flash).
- Check Status: Verify all LEDs indicate proper operation and network connectivity.
Reset & Recovery
- Reset Button: For devices manufactured after 03/2022, use the internal button for:
- <15s: LED test.
- 15–30s: Soft reset (network/login only).
- 30s: Hard reset (full factory reset).
- Web Reset: For firmware 2.11+, full reset can be done via /reset_full_flash URL.
Support & Documentation
- Manuals & Updates: Refer to the official user manual for advanced configuration (https://support.lithernet.de/help/en-gb).